Megger MTOU3 three-phase winding resistance ohmmeter

SKU: 4695814-1-837
In Stock

  • 32 A DC maximum test current
  • 10.1″ high-brightness touchscreen
  • ±0.1% resistance measurement accuracy
  • Automatic adaptive demagnetization cycle

Did you like this product? Add to favorites now and follow the product.

Add to wishlist
Have a Question? Ask a Specialist

(+86) 132-6243-8118 Start Live Chat

Low Prices

Price match guarantee

Guaranteed Fitment.

Always the correct part

In-House Experts.

We know our products

Easy Returns.

Quick & Hassle Free

Description

Powerful Innovation In Winding Resistance Testing Solutions

The Megger MTOU3 three-phase winding resistance ohmmeter is an advanced, true three-phase source and measurement instrument designed for the electro-mechanical testing of power, distribution, and instrument transformers. This device transforms how field engineers and technicians approach transformer testing by offering fast, highly accurate, and safe winding resistance measurement procedures. Its architecture is based on the concept of a one-time lead connection, which enables all subsequent testing—vector confirmation, winding resistance, and demagnetization—without further re-connecting leads. This single-connection setup, coupled with robust safety features such as a key lock, safety interlock, and emergency stop, maximizes both operator safety and efficiency. The MTOU3 reduces the risk of wiring errors or missed connections, offering peace of mind through simplified operation and automated verification. The instrument achieves remarkable accuracy, providing winding resistance up to 32 A and delivers results with an impressive ±0.1% accuracy, ensuring measurement confidence even in critical grid infrastructure projects.

Unrivaled Efficiency With One-Time Lead Connection

The brilliance of the MTOU3 lies in its innovative use of a one-time, color-coded lead connection system with extendable kelvin clamps. Engineered for seamless integration with transformers of varying sizes, these clamps extend up to 7.6 cm (3 inches) and support lead lengths between 5m and 30m, accommodating diverse test setups in substations or workshops. The ability to make all connections during a single ladder climb enhances user safety and dramatically reduces test preparation time, limiting the physical hazard of multiple ascents. Furthermore, the color-coding of leads, connectors, and clamps ensures quick identification and reduces set-up errors, while on-screen guidance matches physical connections to the transformer’s nameplate vector diagram, ensuring every test is conducted correctly from the first attempt. This intuitive, guided process contributes to rapid completion of multiple testing procedures, boosting productivity without sacrificing reliability.

Intuitive Touch Interface And Advanced Data Handling

Transforming transformer testing into an accessible, streamlined experience, the MTOU3 posesses a large 10.1-inch, high-brightness touchscreen display that delivers an intuitive graphical interface. Large, self-explanatory buttons and on-screen vector diagrams walk users through every stage of the job, from connection through measurement and result validation. Data management is equally robust—test data can be automatically grouped by file name, exported to Microsoft Excel, or printed directly using an optional USB thermal printer. The device boasts an internal storage capacity for up to 10,000 sets of three-phase results, all of which can be transferred to a PC via USB and seamlessly integrated into PowerDB or custom testing software. These features greatly minimize post-test administrative work, allowing for effortless report generation, compliance documentation, and long-term result archiving, ultimately streamlining organizational workflow.

Unique Vector Confirmation And Polarity Validation Systems

A groundbreaking aspect of the MTOU3 is its Automatic Vector Confirmation and Polarity Recognition systems—functions rarely found in conventional winding resistance testers. Before each test, the instrument checks and validates that the correct vector group is selected using on-screen vector diagrams. This procedure not only prevents costly mistakes or misreadings, but it also safeguards transformers and test personnel from potential accidents caused by misconnection or misinterpretation. On-load tap changers (OLTC) can be tested without changing leads, allowing the MTOU3 to perform continuity checks for make-before-break transitions and complete OLTC sequences via the “one-touch OLTC” feature. If an anomaly arises, the user interface highlights the affected phase, guiding the operator through a clear validation process, ensuring that only genuine issues are flagged. These capabilities make the MTOU3 an invaluable tool for utilities, transformer OEMs, and service companies striving for error-free transformer maintenance.

Adaptive Demagnetization And Core Protection Technology

Residual core magnetization following DC resistance testing can present severe hazards, such as inadvertent tripping of protection relays when returning transformers to service. The MTOU3 addresses this risk through automatic adaptive demagnetization. Upon completion of winding resistance measurements, the device automatically performs a gentle demagnetization cycle, effectively removing remanence from the transformer core. This built-in protocol eliminates the risk of protection malfunctions, reduces nuisance equipment trips, and ensures safe, smooth transformer energization post-testing. The adaptive nature of the demagnetization algorithm tailors each cycle to the condition of the previously tested windings, optimizing the process for efficiency and transformer safety. This feature directly translates into improved reliability for the primary power infrastructure and enhances the operational readiness of high-voltage assets in the grid.

Specialized Applications Across Utility And Industrial Sectors

The Megger MTOU3 excels in a wide array of transformer testing scenarios, supporting professionals working in power generation, transmission, distribution networks, and heavy industry. It is particularly suitable for:

  • Routine maintenance of large power transformers—where its high accuracy, speed, and safety features minimize downtime.
  • Commissioning of new transformers, offering fast, easy verification of winding resistance and phase relationships.
  • Field analysis of distribution and instrument transformers—its portability and robust construction, with an IP67-rated case during transit, ensures reliable operation under harsh environmental conditions.
  • Tap changer diagnostics, as the device seamlessly conducts winding resistance checks across multiple tap positions while monitoring OLTC continuity, vibration, and motor current.
  • Transformer manufacturing quality control—allowing for automated, consistent data collection and reporting in accordance with IEEE, IEC, and other international testing standards.

The MTOU3 is therefore indispensable for engineers and maintenance teams needing a versatile, high-precision tool for transformer assessment and troubleshooting.

Global Availability And Guarantee Through tpt24 Online Store

For organizations seeking the ultimate in authenticity and service quality, tpt24 stands as the premier online store for the Megger MTOU3 three-phase winding resistance ohmmeter. No matter your location, tpt24 guarantees original Megger products, providing a robust warranty of authenticity and global delivery you can depend on. The store’s reputation for reliability extends from pre-sale consultation and selection guidance to after-sales support, ensuring customers receive not just cutting-edge equipment but also peace of mind. With tpt24, your investment in transformer testing technology is protected, and your laboratory, field service, or utility fleet is equipped with an instrument that exceeds international expectations. Trust tpt24 to deliver genuine MTOU3s, along with all accessories, software, and after-sales care anywhere in the world.

Specifications

Specification Details
Model Megger MTOU3 True Three-phase winding resistance ohmmeter
Applications Power, distribution, instrument transformers
Input Voltage Range 100–240 V AC, 47–63 Hz, 1200 W±10%
Output Voltage Up to 100 V DC, three-phase switched
Output Current Range Up to 32 A (PRO/EXP), Up to 16 A (ADV)
Measuring Modes Wye, delta, zigzag, dual winding excitation
Resistance Range 1.0 μΩ to 30 kΩ (±0.1% ±1μΩ), 30+ kΩ (±0.5%)
Resistance Resolution 5 digits
Dynamic Resistance Test Supported (EXP/PRO, up to 20 kHz sampling)
OLTC Testing Continuity verification, one-touch OLTC operation
Safety Features Emergency stop, key lock, safety interlock
Touchscreen 10.1” 1024×600 px, 1000 NITS, hi-bright
Storage Capability Up to 10,000 three-phase test sets (internal)
Data Export USB, Microsoft Excel, PowerDB compatible
Printing Optional USB thermal printer, 51 mm width
Communication USB interface for PC control/Custom GUI
Dimensions (W x D x H) 55.8 x 28.7 x 19 cm (22 x 11.3 x 7.5 in)
Weight 17 kg (38 lbs)
Environmental Range -20°C to +50°C (operation), -30°C to +70°C (storage)
Humidity/Elevation 0-90% RH, up to 2000m elevation
Ingress Protection IP67 (in transit case)
Compliance Standards IEEE C57.152, IEC 60076-1, AS/NZS, CIGRE, GOST
Lead Accessories Kelvin clamps, 5–30 m leads; color-coded
Special Features Automatic vector confirmation, adaptive demagnetization
Optional Features Motor/vibration monitoring, external temp probe, beacon

Data Sheet

Download Data Sheet Of Megger MTOU3 three-phase winding resistance ohmmeter