KYORITSU POWER METER KEW 6305-01
- 3-Channel Simultaneous Recording
- 60,000 Data Points Storage
- True RMS Measuring Method
- Approx. 10 Days Battery Life
Did you like this product? Add to favorites now and follow the product.
(+86) 132-6243-8118 Start Live Chat
Description
Versatile Leakage and Load Current Logger
The specifications describe a highly effective data logger designed for the simultaneous recording of leakage current and load current. This device, with its 3-channel inputs, provides a powerful solution for professionals who need to monitor electrical systems for both efficiency and safety. Unlike simple multimeters, this logger can capture and store a vast amount of data, making it ideal for diagnosing intermittent problems that are difficult to pinpoint in a single measurement. The ability to measure both types of current simultaneously is a significant advantage, allowing for a comprehensive analysis of the electrical system’s health and performance.
A key feature of this logger is its large storage capacity. With the ability to store up to 60,000 data points, it can conduct long-term monitoring over a period of days or even weeks. The non-volatile memory ensures that all recorded data is safely retained even if power is lost, providing peace of mind during extended logging sessions. This extensive data capacity is crucial for identifying trends, such as gradual increases in leakage current over time, which could indicate a developing insulation fault. Furthermore, the device offers two recording modes, One-time mode and Endless mode, giving the user flexibility in how they manage their data collection.
The logger’s measurement capabilities are finely tuned for accuracy and reliability. It employs a True RMS measuring method, which is essential for obtaining accurate readings of distorted waveforms common in modern electrical systems. This is particularly important for accurately measuring current in environments with non-linear loads, such as those with variable-frequency drives or switched-mode power supplies. The device also features a Lowpass Filter to filter out harmonics, which can interfere with accurate leakage current measurements. This helps in isolating the true leakage current from other electrical noise, ensuring a more precise diagnosis of insulation issues.
The device is equipped with a user-friendly PC software, “KEW LOG Soft2,” which significantly enhances its functionality. This software allows for easy data analysis, visualization of recorded trends, and configuration of the logger’s settings. The USB cable (7148) provides a simple and reliable connection between the logger and a PC. This seamless data transfer and analysis process streamlines the workflow for engineers and technicians, allowing them to quickly interpret the data and generate professional reports. The inclusion of the software makes this product a complete solution for data logging and analysis, not just a data collection tool.
For professionals seeking a reliable and high-quality data logger, the tpt24 online store offers an unparalleled purchasing experience. This store is recognized as the world’s leading online retailer for this specific product, known for its unwavering commitment to providing authentic and top-quality equipment. Every unit sold through tpt24 comes with a guarantee of authenticity and quality, ensuring that customers receive a genuine product that meets all technical specifications. With a robust logistics network, tpt24 delivers to any country, providing a seamless and trustworthy service no matter your location. Their dedication to excellence and customer satisfaction makes them the definitive choice for acquiring this essential tool.
Specialized Applications of Current Logging
This data logger is indispensable for a variety of specialized applications, particularly those related to electrical safety and maintenance. One of its primary uses is for preventive maintenance programs. By continuously monitoring leakage current over time, technicians can detect gradual deterioration of insulation in cables and equipment. A sudden or sustained increase in leakage current can be a clear warning sign of an impending fault, allowing for timely repairs before a dangerous short circuit or fire occurs. This capability turns the device into a proactive tool, shifting maintenance from a reactive to a predictive model.
Another critical application is for diagnosing intermittent equipment faults. Many electrical problems, such as a motor tripping sporadically, are not constant and can be very difficult to catch. By placing the logger on the circuit, technicians can record the current over a period of days. The Trigger Recording Mode is particularly useful for this, as it can be set to start recording when the current exceeds a certain threshold. This allows for the capture of fleeting events that are causing the malfunction, providing a clear waveform of the event that can be analyzed to determine the cause. This feature significantly reduces the time and effort required for troubleshooting, leading to faster repairs and reduced downtime.
The logger is also ideal for load studies and energy audits. In many commercial and industrial settings, understanding the current draw of equipment is essential for balancing loads and ensuring optimal system performance. The logger can be used to monitor the load current of a specific piece of machinery or an entire circuit over a week or more. The data collected can be used to identify peak consumption times, analyze load profiles, and confirm if a circuit is overloaded. This information is invaluable for making decisions about load distribution, equipment scheduling, and for designing more efficient electrical systems.
The Capture Recording Mode provides even more detailed analysis, allowing for the capture of waveforms, which is critical for identifying specific types of faults, such as inrush currents. For example, when a motor starts, it can draw a very high inrush current that can trip a circuit breaker. By capturing this event, engineers can verify the magnitude and duration of the inrush current and determine if the circuit breaker is correctly sized or if there is a more serious issue. The device’s LED warning system, which flickers when a preset current value is exceeded, provides an immediate visual alert of such events, even from a distance.
Specifications
■Normal Recording Mode (AC 50/60Hz, Sine wave, Input: 10% or more of the range at CH1)
| Range | RMS Accuracy |
|---|---|
| 100.0mA | ±2.0%rdg±0.9%f.s.+ Accuracy of Sensor |
| Other ranges | ±1.5%rdg±0.7%f.s.+ Accuracy of Sensor |
| Crest Factor | 2.5 or less: RMS accuracy (sine) + 2%rdg + 1%f.s. |
*Max, Min and Instant Peak values in Normal Recording mode are just reference values:
their accuracies aren’t guaranteed.
■Trigger Recording Mode (AC 50/60Hz sine wave)
| Range | Accuracy |
|---|---|
| 100.0mA | ±3.5%rdg±2.2%f.s.+ Accuracy of Sensor |
| Other ranges | ±3.0%rdg±2.0%f.s.+ Accuracy of Sensor |
■Capture Recording Mode
| Range | Accuracy |
|---|---|
| 100.0mA | ±3.0%rdg±1.7%f.s.+ Accuracy of Sensor |
| Other ranges | ±2.5%rdg±1.5%f.s.+ Accuracy of Sensor |
| Recording mode | Normal, Trigger, Capture |
|---|---|
| Operating system | Successive Approximation (CH1 single synchronized sampling) |
| Rated max. working voltage | AC 9.9Vrms, 14V peak value |
| Number of input channel | 3ch |
| Measuring method | True RMS |
| RMS measuring interval | Approx. 100ms |
| Sampling interval | Normal/Trigger mode : Approx. 1.65ms/CH Capture mode : Approx. 0.55ms (waveform: at every 1.1ms) |
| Current range | 8146 (30A type) : 100.0/1000mA/10.00/30.0A 8147 (70A type) : 100.0/1000mA/10.00/70.0A 8148 (100A type) : 100.0/1000mA/10.00/100.0A 8121 (100A type) : 10.00/100.0A 8122 (500A type) : 50.00/500.0A 8123 (1000A type) : 100.0/1000A 8128/8135 (5A type) : 5.000A/(50.00A) 8127 (100A type) : 10.00A/100.0A 8126 (200A type) : 20.00A/200.0A 8125 (500A type) : 50.00A/500.0A 8124 (1000A type) : 100.0A/1000A 8130 (1000A type) : 100.0/1000A |
| Low battery warning | Battery mark display (in 4 levels) |
| Over-range indication | “OL” mark is displayed when exceeding the measuring range |
| Auto power off | Turns off the instrument automatically if there is no switch operation for about 3 min. (This function doesn’t work during a recording.) |
| Possible measurement time | Approx. 10 days (with alkaline LR6 batteries) |
| Applicable standards | IEC 61010-1:2001 CAT Ⅲ 300V Pollution degree2, IEC 61326 (EMC) |
| Dimension | 111(L)×60(W)×42(D)mm |
| Weight | Approx. 265g |
| Accessories | 7148 (USB cable) 9118 (Carrying case) LR6×4pcs Instruction manual Quick manual USB Notice sheet |
| Optional Accessories | 8146/8147/8148 (Leakage & Load current Clamp Sensor) 8121/8122/8123 (Load current Clamp Sensor) 8124/8125(*1)/8126(*2)/8127(*3)/8128 (Load current Clamp Sensor) 8130(*4)/8135 (Flexible Clamp Sensor) 7185 (Extension cable for sensor) 8320 (AC Adapter) 9135 (Carrying bag) |